Regulation 79 Internationaal Verdrag van Torremolinos voor de beveiliging van vissersvaartuigen, 1977

- FIRE SAFETY MEASURES IN VESSELS OF 55 METRES IN LENGTH AND OVER

(1)

(a) Where more than one hydrant is required to provide the number of jets specified in Regulation 80(2)(a) a fire main shall be provided.

(b) Fire mains shall have no connexions other than those required for fire fighting except for the purpose of washing the deck and anchor chains or operating the chain locker bilge ejector.

(c) Where fire mains are not self-draining, suitable drain cocks shall be fitted where frost damage could be expected.

(2)

(a) The diameter of the fire main and water service pipes shall be sufficient for the effective distribution of the maximum required discharge from two fire pumps operating simultaneously or of 140 cubic metres per hour, whichever is the less.

(b) With the two pumps simultaneously delivering through nozzles specified in Regulation 80(5) the quantity of water specified in sub-paragraph (a) of this paragraph, through any adjacent hydrants, the minimum pressure of 0.25 newtons per square millimetre shall be maintained at all hydrants.