Combustion plants with a rated thermal input exceeding 50 MWth:

1) The rated thermal input of the combustion plant is calculated as the sum of the input of all units connected to a common stack. Individual units below 15 MWth shall not be considered when calculating the total rated thermal input.

Table 1 Limit values for SO2 emissions from combustion plants1)

Fuel type | Thermal input (MWth) | ELV for SO2 mg/m32)

Solid fuels | 50–100 | New plants: 400 (coal, lignite and other solid fuels) 300 (peat) 200 (biomass)

Existing plants: 400 (coal, lignite and other solid fuels) 300 (peat) 200 (biomass)

100–300 | New plants: 200 (coal, lignite and other solid fuels) 300 (peat) 200 (biomass)

Existing plants: 250 (coal, lignite and other solid fuels) 300 (peat) 200 (biomass)

>300 | New plants: 150 (coal, lignite and other solid fuels) (FBC: 200) 150 (peat) (FBC: 200) 150 (biomass)

Existing plants: 200 (coal, lignite and other solid fuels) 200 (peat) 200 (biomass)

Liquid fuels | 50–100 | New plants: 350 Existing plants: 350

100–300 | New plants: 200 Existing plants: 250

>300 | New plants: 150 Existing plants: 200

Gaseous fuels in general | >50 | New plants: 35 Existing plants: 35

Liquefied gas | >50 | New plants: 5 Existing plants: 5

Coke oven gas or blast furnace gas | >50 | New plants: 200 for blast furnace gas 400 for coke oven gas

Existing plants: 200 for blast furnace gas 400 for coke oven gas

Gasified refinery residues | > 50 | New plants: 35 Existing plants: 800

1) In particular, the ELVs shall not apply to:

– Plants in which the products of combustion are used for direct heating, drying, or any other treatment of objects or materials;

– Post-combustion plants designed to purify the waste gases by combustion which are not operated as independent combustion plants;

– Facilities for the regeneration of catalytic cracking catalysts;

– Facilities for the conversion of hydrogen sulphide into sulphur;

– Reactors used in the chemical industry;

– Coke battery furnaces;

– Cowpers;

– Recovery boilers within installations for the production of pulp;

– Waste incinerators; and

– Plants powered by diesel, petrol or gas engines or by combustion turbines, irrespective of the fuel used.

2) The O2 reference content is 6% for solid fuels and 3% for liquid and gaseous fuels.

Note: FBC = Fluidized bed combustion (circulating pressurized, bubbling).