wetzoeker

14b.2.14 — Fixed Fire Detection and Fire Alarm Systems and Automatic Sprinkler, Fire Detection and Fire Alarm Systems Regeling veiligheid zeeschepen

Fixed Fire Detection and Fire Alarm Systems and Automatic Sprinkler, Fire Detection and Fire Alarm Systems

Purpose

The purpose of this section is to detect a fire in the space of origin and to provide for alarm for safe escape and fire-fighting activity. For this purpose, the following functional requirements should be met:

• fixed fire detection and fire alarm system installations should be suitable for the nature of the space, fire growth potential and potential generation of smoke and gases; and

• manually operated call points should be placed effectively to ensure a readily accessible means of notification.

14B.2.14.1 Each separate zone in all accommodation and service spaces, except spaces which afford no substantial fire risk such as void spaces, sanitary spaces, etc., should be provided throughout with an automatic sprinkler, fire detection and fire alarm system of an approved type and complying with the requirements of SOLAS 74, Chapter II-2 Part C, regulation II-2/7 and the IMO FSS Code, Chapter 8, or an equivalent standard acceptable to the Administration. The system should be designed to enable simultaneous operation of all sprinklers fitted in the most hydraulically demanding area. The minimum area for simultaneous operation may be taken as the largest area bounded by ‘A-O’ class bulkheads or the breadth of the vessel squared, whichever is the greater, subject to a maximum of 280m2.

14B.2.14.2 A fixed fire detection and fire alarm system is to be fitted in all enclosed spaces except those containing no significant fire risk (toilets, bathrooms, void spaces, etc). Manually operated call points should be placed to ensure a readily accessible means of notification. The fixed fire detection and fire-alarm system is to be installed in accordance with the requirements of SOLAS II-2/7 and the IMO Fire Safety Systems Code, Chapter 9, and should be audible externally.