14.2.2 — Construction and Arrangement of Steam Room Regeling veiligheid zeeschepen

Construction and Arrangement of Steam Room

14.2.2.1 The perimeter of the steam room may include changing rooms, showers and toilets.

14.2.2.2 Bathrooms with direct access to suite may be considered as part of it. In such cases, the door between suite and the bathroom need not comply with fire safety requirements.

14.2.2.3 If a steam generator of more than 5 kW is contained within the perimeter, the suite boundary should be constructed to an A-0 standard, or B-0 for Short Range Yachts. If a steam generator of more than 5 kW is not contained within the perimeter the steam generator should be protected by A-0 standard divisions, or B-0 for Short Range Yachts and pipes leading to the discharge nozzles should be lagged.

14.2.2.4 If a suite arrangement contains a sauna then the requirements contained in 14.2.1 are applicable, regardless of the steam generator location.

14.2.2.5 All spaces within the perimeter are to be protected by a fire detection and alarm system.